Recommended Tools & Consumables
No Recommended Tools & Consumables specified.
Hardware & Accessories
-
-
Carrier Transicold X2100A controller requires HRN-RCCCAAD harness to connect to the refrigeration unit.
-
HRN-RW03K4 will be used to get your power, ignition and ground for the Go Rugged device.
-
-
-
In this example installation, we connect directly to the battery of the refrigeration unit for our constant power and ground connections using HRN-RW03K4.
-
RED Battery Wire - Locate and verify a constant +12/24V Battery source.
-
BLACK Ground Wire - Locate and verify a ground source. The reference point directly comes from the battery terminal, and the refrigeration units chassis.
-
Always use a digital multimeter to locate and verify your connection points.
-
-
-
YELLOW Ignition Wire - The ignition wire must be connected to the refrigeration unit controller ignition source. Wire should be labeled HC11-1RS2
-
Verify that the ignition interface point has 12V/24V when the refrigeration unit's START / RUN switch is ON.
-
Verify that the ignition interface point has 0V when the refrigeration unit’s START / RUN switch is OFF.
-
You may need to open the controller panel to access the wires for your ignition source.
-
-
-
Connect the HRN-RCCCAADV harness to the Serial Port 3-way connector located near the right compartment of the unit.
-
✱ NOTE: If the serial port is not free, contact the support team.
-